Cressall

Renewable Energy

Cressall resistors for wind power generation systems

Harnessing the wind is one of the cleanest, most sustainable ways to generate electricity. Wind power produces no toxic emissions and none of the emissions that contribute to global warming. This, and the fact that wind power is one of the most abundant and increasingly cost effective energy resources makes it a viable alternative to burning fossil fuels.

Cressall Resistors designs and manufactures a range of components that form essential parts of any wind-farm installation:

  • Pre-Insertion Resistors
  • Crowbar Resistors
  • Neutral Earthing Resistors
  • Dynamic Braking Resistors
  • Load test
  • Resistors for Static VAR Compensators

Wind Turbines

Pre-insertion resistor (PIR)

Wind turbines are connected to the distribution network through step-up transformers, and when these are energised high inrush currents and overvoltages may be created on the distribution network. These can cause problems with other network equipment. There are two ways to limit the level of voltage fluctuation:

  • Reduce the number of transformers energised at one time – this reduces the inrush current but adds increased system complexity and cost as multiple HV switches will be needed along with a switching control system.
  • Insert a pre-insertion resistor (PIR) into the circuit during energisation. The PIR is a three phase resistor, insulated for the full system voltage – typically 33kV – fitted with two isolating devices. No other switchgear or staged switching system is required. A PIR needs to have a high thermal mass to absorb the energies involved in the short time that the inrush currents are present, yet be compact enough to locate efficiently within the transformer sub station. Cressall PIRs are in service at many wind-farms in the UK and Eire.

Crowbar resistors

Grid disturbances can produce high transient currents and voltages, which lead to high voltage and currents on the turbine generator rotors.

To prevent damage to the power electronics of the converters a protection circuit (or Crowbar) is used to short circuit the rotor windings through a resistor for the period of the disturbance.

These resistors need to have a low inductance (to restrict the impact of the high transient frequency) and be capable of withstanding high currents for short periods of time without damage.


Load Test ResistorsLoad Test resistors

Load test resistors are one of the simplest ways to prove the capability of a power generation and storage system – by physically making the device do the job of work it is designed to do, without the risk to equipment which could be harmed in the event of a power failure. By using separate load test resistors you a have a safe, reliable and repeatable approach to testing.

Cressall can manufacture either custom built designs or solutions straight off the shelf to meet your testing needs; these load banks can be simple, long life naturally cooled or compact fan cooled depending on the location, space envelope and control requirements, for any voltage and power rating from 100V to 33kV and from 1kW to 100MW.


Neutral earthing resistors (NERs)

If an earth fault occurs on the generation network the resulting high earth fault currents may damage the stator windings on the turbine generators. Neutral Earthing Resistors limit these currents during the time before the protection system operates. They are connected between the neutral of the transformers and earth, restricting the fault current to a level low enough to limit the potential for damage yet high enough to meet the requirements of the system protection scheme.

NERs

Like pre-insertion resistors, NERs need to have a high thermal mass to absorb the energies of the earth fault yet be compact enough to locate efficiently within the transformer sub station.


Dynamic Braking Resistors (DBRs)

On fixed speed wind generators changes in wind speed can have a detrimental impact on the stability of the system. These changes in wind speed can be mitigated in several ways – changing the pitch of the turbine blades, using a static compensator or by inserting a braking resistor in series with the generator circuit. The latter offers the benefit of relatively low cost combined with effective voltage stabilisation performance. Under normal (steady state conditions) the resistor is bypassed. In the event of a problem the bypass switch is opened, bringing the resistor into circuit to dissipate excess power.
DBRs

Resistors for this application need to have enough thermal mass to absorb the short term duty yet still be able to dissipate energy effectively to allow for frequent operations in changeable conditions.

Resistors for static VAR compensators (SVCs)

Static VAR compensators are used as part of large AC transmission systems to regulate the transmission voltage and to stabilize the system. This is particularly important in large offshore wind generation schemes at the point where they interface with an existing grid network. The impact of changing wind speeds on power quality can be serious. By switching in capacitive or reactive components the SVC can limit the impact of these fluctuations and improve availability.

SVCs

With such large power electronic systems it is essential that the components are able to meet the stringent requirements, high insulation levels, high power and low inductance (pure resistors). Cressall has supplied resistors for SVC applications around the world and for most environments.